Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STILL NEED TO COMPLETE 3, 4, 5 & 6 FROM PREVIOUS INSPECTION 2) A PERMIT IS REQUIRED FOR NEW A/C INSTALLATION |
|
| 06/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TIGHTEN BOND CLAMPS 2. GROUND RODS TO BE MINIMUM 6' APART 3. #6 & SMALLER GROUND BARE OR GREEN ENTIRE LENGTH 4. #6 & SMALLER NEUTRAL WHITE ENTIRE LENGTH 5. CKTS WITH SHARED NEUTRAL NEED TO TERMINATE ON SEPARATE PHASES 6. BREAKERS TO BE MARKED CORRECTLY & CLEARLY (LEGIBLE) |
|
| 06/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) GATE LOCKED |