Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/21/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* RECALL AFTER TEP TIE IN |
|
| 06/19/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE PAINT AT GAS PIPE BOND CONNECTION NEC 250.12 2. INSTALL TERMINAL LUGS IN METER SECTION FOR OVERHEAD POSITION. SEE STICKER IN METER SECTION NEC 110.3 3. GROUND RODS TO BE MIN. 6' APART - NEC 350.53 & 250.56 4. ALL GROUNDING ELECTRODES AT EACH BUILDING SHALL BE BONDED TOGETHER NEC 250.50 5. PLEASE UNCOVER TOP 12" OF GROUND RODS TO VERIFY LISTING MARK 6. PLEASE VERIFY PERMIT FOR NEW ROOFTOP A/C UNIT AT 3007 |