Permit: T07EL01131

Parcel: 12302160D


Addresses:

3005 E SENECA ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/18/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/21/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) RECALL AFTER TEP TIE IN
06/19/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE PAINT AT GAS PIPE BOND CONNECTION NEC 250.12
2. INSTALL TERMINAL LUGS IN METER SECTION FOR OVERHEAD POSITION. SEE STICKER IN METER SECTION
NEC 110.3
3. GROUND RODS TO BE MIN. 6' APART - NEC 350.53 & 250.56
4. ALL GROUNDING ELECTRODES AT EACH BUILDING SHALL BE BONDED TOGETHER NEC 250.50
5. PLEASE UNCOVER TOP 12" OF GROUND RODS TO VERIFY LISTING MARK
6. PLEASE VERIFY PERMIT FOR NEW ROOFTOP A/C UNIT
AT 3007