Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL SMOKE DETECTORS AT SLEEPING AREAS, BEDROOMS 2) INSTALL GFI PROTECTED RECEPTACLES IN BATHROOM, KITCHEN SINK AREA 3) COVER PLATES MISSING 4) SUPPORT RECEPT BOXES UNDER SERVICE PANEL AND TERMINATE CONDUIT PROPERLY 5) DEAD FRONT COVER MISSING IN SERVICE PANEL 6) ROMEX WIRING FOR ADDITION IN BACK OF HOUSE NOT TO CODE 7) VERIFY PERMITS, PLANS APPROVED INSPECTIONS FOR ADDITION TO HOUSE, YOU CAN CHECK RECORDS AT 201 N. STONE |