Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/22/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER TEP TIE IN |
|
| 06/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING. CANNOT USE EMT & MINNIE NEC 230.28 2. CONNECT SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER SECTION - NEC 110.3 3. WIPE UP EXTRA ANTI-OXIDATION COMPOUND 4. HOW ARE SERVICE DROP CLEARANCE ABOVE ROOF GOING TO BE MET? NEC 230.26 & 230.24 |