Permit: T07EL01119

Parcel: 134210770

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/22/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECALL AFTER TEP TIE IN
06/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING. CANNOT USE EMT & MINNIE
NEC 230.28
2. CONNECT SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER SECTION - NEC 110.3
3. WIPE UP EXTRA ANTI-OXIDATION COMPOUND
4. HOW ARE SERVICE DROP CLEARANCE ABOVE ROOF GOING TO BE MET? NEC 230.26 & 230.24