Permit: T07EL01114

Parcel: 134080020


Addresses:

819 S SARNOFF DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY NEUTRAL CLOSER TO WEATHERHEAD
2. IDENTIFY CIRCUITS AT PANEL PER - NEC 408.4
3. GROUNDING CONDUCTORS #6 AND SMALLER TO BE MARKED CONTINUOUSLY - NEC 250.119
4. NEUTRAL CONDUCTORS #6 AND SMALLER TO BE MARKED CONTINUOUSLY - NEC 200.6
5. BOND AROUND REDUCING WASHERS PER NEC 250.96
HAVE HIGH RESISTANCE CONNECTION
6. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
NEC 110.3
7. SERVICE ENERGIZED PRIOR TO APPROVALS