Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IDENTIFY NEUTRAL CLOSER TO WEATHERHEAD 2. IDENTIFY CIRCUITS AT PANEL PER - NEC 408.4 3. GROUNDING CONDUCTORS #6 AND SMALLER TO BE MARKED CONTINUOUSLY - NEC 250.119 4. NEUTRAL CONDUCTORS #6 AND SMALLER TO BE MARKED CONTINUOUSLY - NEC 200.6 5. BOND AROUND REDUCING WASHERS PER NEC 250.96 HAVE HIGH RESISTANCE CONNECTION 6. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL NEC 110.3 7. SERVICE ENERGIZED PRIOR TO APPROVALS |