Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/02/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) INSTALL ROOF JACK AT MAST PENETRATION 2) DO NOT HAVE PROPER CLEARANCE ABOVE ROOF ON SERVICE CONDUCTORS. NEED 8' MIN NEC 230.26 AND 230.24 3) NEED TO INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT NEC 230.28 4) PROPERLY IDENTIFY WHITE WIRES USED AS PHASE CONDUCTORS NEC 200.7 5) SEAL OPENING IN BACK OF PANEL WITH NON COMBUSTIBLE MATERIAL 6) REMOVE PAINT AT GROUND CLAMP CONNECTIONS NEC 250.12 7) THIS IS A TEMPORARY CLEARANCE PER JASON JAWORSKY. THE REASON FOR THE CLEARANCE IS EXTREME TEMPERATURES AND MEDICAL CONDITION OF HOME OWNERS. NO ONE TO GO ON ROOF IN AREA OF SERVICE CONDUCTORS. THIS SERVICE NEEDS TO BE RECALLED IN 10 WORKING DAYS AND HOUSE SERVICE CONDUCTOR CLEARANCE TAKEN CARE OF |
|
| 06/29/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |