Permit: T07EL01112

Parcel: 134250060


Addresses:

1126 S MANN AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/11/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/02/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) INSTALL ROOF JACK AT MAST PENETRATION
2) DO NOT HAVE PROPER CLEARANCE ABOVE ROOF ON SERVICE CONDUCTORS. NEED 8' MIN NEC 230.26 AND 230.24
3) NEED TO INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT NEC 230.28
4) PROPERLY IDENTIFY WHITE WIRES USED AS PHASE CONDUCTORS NEC 200.7
5) SEAL OPENING IN BACK OF PANEL WITH NON COMBUSTIBLE MATERIAL
6) REMOVE PAINT AT GROUND CLAMP CONNECTIONS NEC 250.12
7) THIS IS A TEMPORARY CLEARANCE PER JASON JAWORSKY. THE REASON FOR THE CLEARANCE IS EXTREME TEMPERATURES AND MEDICAL CONDITION OF HOME OWNERS. NO ONE TO GO ON ROOF IN AREA OF SERVICE CONDUCTORS. THIS SERVICE NEEDS TO BE RECALLED IN 10 WORKING DAYS AND HOUSE SERVICE CONDUCTOR CLEARANCE TAKEN CARE OF
06/29/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR