Permit: T07EL01111

Parcel: 126190390


Addresses:

538 S CATALINA AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/08/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONNECT EQUIPMENT GROUNDING CONDUCTOR TO 8X8 JUNCTION BOX.
2. HAVE 14 CURRENT CARRYING CONDUCTORS IN 3/4" EMT NEED TO DERATE AMPACITY PER NEC 310.15 & 310.16
3. OK GROUND RODS
4. OK GAS & WATER BOND