Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONNECT EQUIPMENT GROUNDING CONDUCTOR TO 8X8 JUNCTION BOX. 2. HAVE 14 CURRENT CARRYING CONDUCTORS IN 3/4" EMT NEED TO DERATE AMPACITY PER NEC 310.15 & 310.16 3. OK GROUND RODS 4. OK GAS & WATER BOND |