Permit: T07EL01107

Parcel: 13815010A


Addresses:

6524 S 6TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
06/14/2007 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
06/13/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WIRING TO WELL NOT TO CODE-INSTALL PER CODE OR REMOVE
2) RECEPTS OVER SINK IN KITCHEN NEED TO BE GFI PROTECTED
3) SUB PANEL OVERFUSED, SIZE PER WIRE SIZE, NOT WHATEVER WILL FIT
4) INSTALL SMOKE DETECTORS IN SLEEPING AREAS
5) WIRING ON ROOF BY SERVICE NOT TO CODE
6) WORK TO BE DONE BY QUALIFIED ELECTRICIAN OR LICENSED CONTRACTOR