Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2007 | ELECTRIC - FINAL | Approved | INCR CLEARED PER R. HOLLANDER | |
| 08/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH PREVIOUS ITEMS 2 (7/31/07) AND 3, 6 AND 10 (6/11/07) NO FURTHER INSPECTIONS UNTIL REFEE PAID |
|
| 07/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Provide bush to protect cables from sharp metal edges Sheathing to extend 1/4" into enclosure Install all strands under lugs Tap splice to be listed for al/cu Fill unused openings with approved parts |
|
| 06/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY ANGEL |
|
| 06/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH PREVIOUS INSPECTION ITEMS 2, 3, 5, 6 , 10 AND 9 |
|
| 06/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT CONDUIT ON SIDE OF PANEL 2. ENTRANCES THROUGH METER SECTION/AREA NOT ALLOWED 3. CORRECTLY IDENTIFY UNINSULATED NEUTRAL 4. MODIFICATION OF LUGS NOT ALLOWED 5. CONDUCTORS LARGER THAN #8 TO BE STRANDED 6. GROUNDING EQUIPMENT CONDUCTOR TO BE SIZED PER 250.122 7. CONDUCTOR AMPACITY TO BE AS PER 310.16 8. WE HAVE A PARALLEL PATH FOR OUR GROUNDING ELECTRODES CONDUCTOR. 9. ONLY ONE CONDUCTOR TO LUG TERMINATION 10. NO MORE THAN 360 DEG. IN A CONDUIT RUN |