Permit: T07EL01104

Parcel: 133181140


Addresses:

7042 E 3RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/13/2007 ELECTRIC - FINAL Approved INCR CLEARED PER R. HOLLANDER
08/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH PREVIOUS ITEMS 2 (7/31/07) AND 3, 6 AND 10 (6/11/07)

NO FURTHER INSPECTIONS UNTIL REFEE PAID
07/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Provide bush to protect cables from sharp metal edges
Sheathing to extend 1/4" into enclosure
Install all strands under lugs
Tap splice to be listed for al/cu
Fill unused openings with approved parts
06/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY ANGEL
06/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH PREVIOUS INSPECTION ITEMS 2, 3, 5, 6 , 10 AND 9
06/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT CONDUIT ON SIDE OF PANEL
2. ENTRANCES THROUGH METER SECTION/AREA NOT ALLOWED
3. CORRECTLY IDENTIFY UNINSULATED NEUTRAL
4. MODIFICATION OF LUGS NOT ALLOWED
5. CONDUCTORS LARGER THAN #8 TO BE STRANDED
6. GROUNDING EQUIPMENT CONDUCTOR TO BE SIZED
PER 250.122
7. CONDUCTOR AMPACITY TO BE AS PER 310.16
8. WE HAVE A PARALLEL PATH FOR OUR GROUNDING ELECTRODES CONDUCTOR.
9. ONLY ONE CONDUCTOR TO LUG TERMINATION
10. NO MORE THAN 360 DEG. IN A CONDUIT RUN