Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BATH GFI HAS REVERSE POLARITY 2) BASE BOARD HEATERS TO BE PROPERLY WIRED WITH ROMEX INTO J-BOX WITH PROPER CONNECTOR AND GROUND SCREW. RECEPTACLE NOT ALLOWED ABOVE HEATER 3) SUB PANEL MISSING PROPER COVER SCREWS 4) FINISH ALL PREVIOUS CORRECTION REQUEST 5) WHERE IS DNR REPORT |
|
| 09/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOXES AT COMBUSTIBLES TO BE FLUSH 314.20 2. BATHROOM RECEPTACLES TO BE GFCI PROTECTED 3. CONDUIT RACEWAY TO BE CONTINUOUS TO PANEL & CONNECT 4. PLEASE VERIFY LISTING FOR CORD & PLUG CONNECTION WITH BASE BOARD HEATERS 5. RECEPTACLES NOT ALLOWED ABOVE BASEBOARD HEATERS 6. DISCONNECT COVER TO OPEN 90 DEG. 7. USE PROPER FITTINGS WITH HUBS & APPROVED HARDWARE |
|
| 09/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* DOOR LOCKED |
|
| 08/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. AT SERVICE DISCONNECT - HUB TO BE RAIN TIGHT, IDENTIFY DISCONNECT WITH SOMETHING SUITABLE FOR ENVIRONMENT - NOT SHARPIE, ROMEX SHEATHING TO EXTEND INTO ENCLOSURE AND USE PROPER ROMEX CONNECTOR. 2. INSIDE UNIT - INSTALL NEW SMOKE DETECTORS IN BEDROOM AND OUTSIDE OF BEDROOM (BATTERY OK) MINIMUM 36" FROM VENTS AND ON CEILINGS. REPLACE ALL PAINTED OVER DEVICES INSTALL PROPERLY SIZED FUSES FOR BRANCH CKT'S SECURE BASEBOARD HEATERS TO WALLS PROVIDE ORIGINAL DNR VIOLATION REPORT CHECK THESE IN UNIT #4 ALSO, ELECTRICAL CONTRACTOR TO PROVIDE COMPLETE DESCRIPTION OF WORK DONE. |