Permit: T07EL01098

Parcel: 10607010B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/16/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BATH GFI HAS REVERSE POLARITY
2) BASE BOARD HEATERS TO BE PROPERLY WIRED WITH ROMEX INTO J-BOX WITH PROPER CONNECTOR AND GROUND SCREW. RECEPTACLE NOT ALLOWED ABOVE HEATER
3) SUB PANEL MISSING PROPER COVER SCREWS
4) FINISH ALL PREVIOUS CORRECTION REQUEST
5) WHERE IS DNR REPORT
09/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOXES AT COMBUSTIBLES TO BE FLUSH 314.20
2. BATHROOM RECEPTACLES TO BE GFCI PROTECTED
3. CONDUIT RACEWAY TO BE CONTINUOUS TO PANEL & CONNECT
4. PLEASE VERIFY LISTING FOR CORD & PLUG CONNECTION WITH BASE BOARD HEATERS
5. RECEPTACLES NOT ALLOWED ABOVE BASEBOARD HEATERS
6. DISCONNECT COVER TO OPEN 90 DEG.
7. USE PROPER FITTINGS WITH HUBS & APPROVED HARDWARE
09/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
DOOR LOCKED
08/28/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. AT SERVICE DISCONNECT - HUB TO BE RAIN TIGHT, IDENTIFY DISCONNECT WITH SOMETHING SUITABLE FOR ENVIRONMENT - NOT SHARPIE, ROMEX SHEATHING TO EXTEND INTO ENCLOSURE AND USE PROPER ROMEX CONNECTOR.
2. INSIDE UNIT - INSTALL NEW SMOKE DETECTORS IN BEDROOM AND OUTSIDE OF BEDROOM (BATTERY OK) MINIMUM 36" FROM VENTS AND ON CEILINGS.

REPLACE ALL PAINTED OVER DEVICES
INSTALL PROPERLY SIZED FUSES FOR BRANCH CKT'S
SECURE BASEBOARD HEATERS TO WALLS
PROVIDE ORIGINAL DNR VIOLATION REPORT
CHECK THESE IN UNIT #4 ALSO, ELECTRICAL CONTRACTOR TO PROVIDE COMPLETE DESCRIPTION OF WORK DONE.