Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE LISTED MAST BRACING. CANNOT USE MINERALLIC STRAP -- NEC 230.28 2. CONNECT SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER SECTION. SEE INSTRUCTIONS ON PANEL DOOR. NEC 110.3 |