Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/06/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* WAITING ON PLAN REVISIONS |
|
| 05/19/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED PLANS |
|
| 05/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT CONDUIT ABOVE PANEL & TIGHTEN FITTING 2. FINISH PREVIOUS ITEMS |
|
| 04/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. LABEL DIRECTORIES AS PER 708.4 2. IF DEMO'D THEN NO CONNECTIONS TO BREAKERS 3. MAINTAIN WORKING CLEARANCES 4. FINISH #1 OF PREVIOUS INSPECTION INTERIOR: 1. SUPPORT M/C CABLES AS PER CODES 2. NEUTRALS NOT TO SHARE SAME PHASE 3. VERIFY DERATING PER 310.15 4. EQUIPMENT GROUNDING CONDUCTORS TO BE AS PER 250.122 5. PLANS TO REFLECT WORK DONE TO INTERIOR |
|
| 04/07/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 03/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CADWELD FOR GEC NOT ATTACHED 2. MAINTAIN WORKING CLEARANCES AT GENERATOR MAIN 3. DOOR TO OPEN 90 DEG. 4. INSTALLATION OF EQUIPMENT NOT AS PER PLANS 5. PLEASE VERIFY MANUFACTURES DRILLING & LUGS ON NEUTRAL BAR OF GENERATOR OR HAVE THIRD PARTY NRTL EVALUATE 6. HAVE EQUIPMENT UNLOCKED AND WILL DO INTERIOR NEXT TIME |
|
| 03/11/2008 | ELECTRIC - FINAL | Cancelled | CANCELLED PER FERNANDO OF MEHL ELECTRIC #490-5225 | |
| 03/11/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |