Permit: T07EL01081

Parcel: 127035460


Addresses:

660 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/25/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/10/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1. RECEIVED LETTER OF TORQUE
2. RECEIVED MEGGAR TEST REPORT
3. COMPLETE ITEM #1 FROM INSPECTION ON 12/6/07
GROUND RODS INSTALLED AT THIS TIME MISSING GEC
12/06/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL GROUND RODS @ GENERATOR PER PLAN
2. NEED REVISION TO PLANS FOR CHANGE IN FEEDER FROM GENERATOR
3. OK GROUND RODS & GROUNDING ELECTRODE CONDUCTOR FOR SES & DISCONNECTS AT BUILDING
4. OK WATER BOND
5. OK 2 - 3" PVC & 1 - 1" PVC FOR GENERATOR
6. PERFORM MEGGAR CHECK ON FEEDERS & HAVE REPORT AVAILABLE AT NEXT INSPECTION. IF CONDUCTORS DO NOT PASS MEGGAR TEST WILL NEED TO INSTALL NEW CONDUCTORS & REMOVE LB'S FROM INSTALLATION
7. REPAIR DAMAGED CONDUCTOR @ CENTER LB
12/04/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. CALL IN BOTH ACTIVITIES FOR PROJECT
2. HAVE APPROVED PLANS ON SITE
3. PROTECT CONDUCTORS FROM PHYSICAL DAMAGE
4. CANNOT USE SHEETMETAL SCREWS FOR GROUND ATTACHMENT
5. PROVIDE LETTER OF TORQUE
6. CONNECT DISCONNECTS TO GROUNDING ELECTRODE
7. REMOVE MAIN BONDING JUMPERS @ DISCONNECTS