Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/10/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. RECEIVED LETTER OF TORQUE 2. RECEIVED MEGGAR TEST REPORT 3. COMPLETE ITEM #1 FROM INSPECTION ON 12/6/07 GROUND RODS INSTALLED AT THIS TIME MISSING GEC |
|
| 12/06/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL GROUND RODS @ GENERATOR PER PLAN 2. NEED REVISION TO PLANS FOR CHANGE IN FEEDER FROM GENERATOR 3. OK GROUND RODS & GROUNDING ELECTRODE CONDUCTOR FOR SES & DISCONNECTS AT BUILDING 4. OK WATER BOND 5. OK 2 - 3" PVC & 1 - 1" PVC FOR GENERATOR 6. PERFORM MEGGAR CHECK ON FEEDERS & HAVE REPORT AVAILABLE AT NEXT INSPECTION. IF CONDUCTORS DO NOT PASS MEGGAR TEST WILL NEED TO INSTALL NEW CONDUCTORS & REMOVE LB'S FROM INSTALLATION 7. REPAIR DAMAGED CONDUCTOR @ CENTER LB |
|
| 12/04/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. CALL IN BOTH ACTIVITIES FOR PROJECT 2. HAVE APPROVED PLANS ON SITE 3. PROTECT CONDUCTORS FROM PHYSICAL DAMAGE 4. CANNOT USE SHEETMETAL SCREWS FOR GROUND ATTACHMENT 5. PROVIDE LETTER OF TORQUE 6. CONNECT DISCONNECTS TO GROUNDING ELECTRODE 7. REMOVE MAIN BONDING JUMPERS @ DISCONNECTS |