Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE NEC 110.26 2. FINISH DRIVING GROUND RODS 3. A GAS BOND IS NEEDED 4. ONLY ONE GROUNDED CONDUCTOR TERMINATION PER LUG NEC 408.21 5. PLEASE VERIFY SUNLIGHT RESISTANCE MARKING ON SERVICE CONDUCTOR. 310.8 (D) |