Permit: T07EL01064

Parcel: 107010010

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/17/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/08/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED TO PAY REINSPECTION FEE

AT SERVICE
1. GROUND & NEUTRAL NOT ALLOWED UNDER SAME LUG
NEC 110.14, 408.21
2. NEED BUSHING FOR FEEDERS - NEC 352.46
3. FEEDER TO HOME COVERED WITHOUT INSPECTION
NEC 300.5

AT SUB-PANEL
1. STRAP CONDUITS - NEC 352.30
2. GROUND PANEL ENCLOSURE - NEC 250.110
3. SECURE PANEL TO STRUCTURE - NEC 110.13A
4. NEED BUSHINGS FOR PVC - NEC 352.46
5. MULTIPLE GROUNDS UNDER LUG AT J-BOX
NEC 110.14, 110.33
6. WIRE NUTS UNDERSIZED AT J-BOX
NEC 110.3 B
7. RANGE AND DRYER TO BE 4-WIRE CKT
NEC 550.16, 250.140

PARTIAL INSPECTION PROVIDE INTERIOR ACCESS
07/31/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES LAST INSP.
06/12/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*