Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/08/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED TO PAY REINSPECTION FEE AT SERVICE 1. GROUND & NEUTRAL NOT ALLOWED UNDER SAME LUG NEC 110.14, 408.21 2. NEED BUSHING FOR FEEDERS - NEC 352.46 3. FEEDER TO HOME COVERED WITHOUT INSPECTION NEC 300.5 AT SUB-PANEL 1. STRAP CONDUITS - NEC 352.30 2. GROUND PANEL ENCLOSURE - NEC 250.110 3. SECURE PANEL TO STRUCTURE - NEC 110.13A 4. NEED BUSHINGS FOR PVC - NEC 352.46 5. MULTIPLE GROUNDS UNDER LUG AT J-BOX NEC 110.14, 110.33 6. WIRE NUTS UNDERSIZED AT J-BOX NEC 110.3 B 7. RANGE AND DRYER TO BE 4-WIRE CKT NEC 550.16, 250.140 PARTIAL INSPECTION PROVIDE INTERIOR ACCESS |
|
| 07/31/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES LAST INSP. |
|
| 06/12/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* |