Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO COMPLIANCE WITH NOTE #6 LAST INSP. |
|
| 06/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BREAKERS LISTED FOR USE IN PANEL 2. COMPLETELY DRIVE GROUND RODS 3. CANNOT USE CHASE NIPPLE FOR CONNECTION OF EMT TO PANEL USE LISTED FITTING 4. CANNOT USE CHASE NIPPLE FOR CONNECTION OF EMT TO PANEL USE LISTED FITTING 5. SECURE #4 GEC TO BUILDING SURFACE 6. SERVICE CABLES NEED TO BE MARKED & LISTED FOR SUNLIGHT RESISTANCE 7. INSTALL ROOF JACK 8. INSTALL BUBBLE COVER ON GFI RECEPT AT PANEL 9. SERVICE ENERGIZED PRIOR TO APPROVALS |