Permit: T07EL01054

Parcel: 134111010

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
INSTALL BREAKERS LISTED FOR USE IN GE SUB-PANEL
08/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
Lock up dogs in the yard.| 910*
PLEASE HAVE DOGS LOCKED UP FOR INSPECTION
06/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LOAD CONDUCTORS NOT TO EXIT THROUGH TOP END WALL MANUFACTURES INSTRUCTIONS/REQUIREMENT - NEC 110.3
2. LABEL CIRCUITS IN PANEL - NEC 408.4
3. NEED TO BOND GAS & WATER PIPING - NEC 250.104
4. NEUTRAL CONDUCTORS #6 AND SMALLER TO BE IDENTIFIED CONTINUOUSLY - NEC 200.6
5. INSTALL LISTED MAST BRACING. CANNOT USE EMT & MINNIE NEC 230.28
6. NEED TO HAVE PROPER BENDING SPACE OF CONDUCTORS IN METER SECTION -- NEC 312.6
7. CANNOT FEED THROUGH ONE PANEL ENCLOSURE TO FEED ANOTHER - NEC 312.8
8. SEAL ALL UNUSED OPENINGS IN PANELS - NEC 110.12
9. CANNOT USE SHEETMETAL SCREWS FOR CONNECTION OF EQUIPMENT GROUNDS -- NEC 250.8