Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ITEMS FROM PREVIOUS INSPECTION 2. NEED DETAILED PANEL DIRECTORY PER NEC 408.4 3. PROTECT ROMEX WIRE FROM DAMAGE & ABRASION WHERE IT ENTERS EMT PER NEC 300.15 4. GROUND 6" X 6" JUNCTION BOX NEC 250.148 5. ROMEX WIRES NEED TO BE CONNECTED TO JUNCTION BOX WITH CONNECTIONS. CANNOT USE 3/4" PLASTIC BUSHINGS. 6. SEAL ALL UNUSED OPENINGS IN JUNCTION BOX 7. EXPLAIN WHAT IS GOING ON WITH UNCONNECTED WIRES AT JUNCTION BOX. 8. PROTECT GROUNDING ELECTRODE CONDUCTOR RUN ACROSS SIDEWALK FROM PHYSICAL DAMAGE. 9. CANNOT INSTALL PANEL IN CLOTHES CLOSET 10. VERIFY WIRE SIZE TO SUB-PANEL IS #4 A.W.G 11. CLOSE ALL OPENINGS IN PANEL DEAD FRONT WITH BREAKER FILLED PLATES. |