Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/05/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) REMOVE PAINT AT GROUND CLAMP CONNECTION AT WATER PIPE NEC 250.12 2) INSTALL PROPER CLAMP ON GROUND ROD TO BE LISTED AND MARKED FOR DIRECT BURY AND USE OF GROUND RODS (CLAMP USED TO CONNECT WATER BOND) 3) VEIFY GAS PIPE BONDING |