Permit: T07EL01047

Parcel: 110030460


Addresses:

3247 N SYCAMORE AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01047

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/05/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND GAS & WATER TO PANEL SERVING STRUCTURE PER NEC 250.104
2. NEED MIN. 18" CLEARANCE ABOVE ROOF ON SERVICE CONDUCTORS PER 230.24
3. CONDUCTORS EXPOSED TO DIRECT SUNLIGHT SHALL BE MARKED "SUNLIGHT RESISTANT" - NEC 310.8
4. REMOVE PAINT AT GROUND CLAMP CONNECTIONS
PER NEC 250.12
5. MARK SERVICE DISCONNECT PER NEC 230.70
6. BOND AROUND REDUCING WASHERS PER NEC 250.96
7. BACK FED BREAKERS TO BE SECURED IN PLACE BY ADDITIONAL FASTENER -- NEC 408.16
8. SERVICE ENERGIZED PRIOR TO APPROVAL