Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND GAS & WATER TO PANEL SERVING STRUCTURE PER NEC 250.104 2. NEED MIN. 18" CLEARANCE ABOVE ROOF ON SERVICE CONDUCTORS PER 230.24 3. CONDUCTORS EXPOSED TO DIRECT SUNLIGHT SHALL BE MARKED "SUNLIGHT RESISTANT" - NEC 310.8 4. REMOVE PAINT AT GROUND CLAMP CONNECTIONS PER NEC 250.12 5. MARK SERVICE DISCONNECT PER NEC 230.70 6. BOND AROUND REDUCING WASHERS PER NEC 250.96 7. BACK FED BREAKERS TO BE SECURED IN PLACE BY ADDITIONAL FASTENER -- NEC 408.16 8. SERVICE ENERGIZED PRIOR TO APPROVAL |