Permit: T07EL01045

Parcel: 133222640


Addresses:

425 N BAHAMAS DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HIGHEST AVAILABLE BREAKER NOT HIGHER THAN 6'7"
2. IDENTIFY UNINSULATED GROUNDED CONDUCTOR 200.6
3. VERIFY BOX FILL AT 4" SQ
4. A LISTED BRACE KIT IS NEEDED
5. USE AN APPROVED ROOF JACK TO SEAL ROOF