Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE - 110.26 2. A PERMANENT METAL ADDRESS LABEL IS NEEDED 3. USE APPROVED FITTING WITH L.B - CHASE NIPPLE NOT APPROVED. 4. ONLY ONE GROUNDED CONDUCTOR PER LUG - 408.21 5. LABEL BREAKERS 6. BOND JUNCTION BOX ENCLOSURE 7. A LISTED BRACE KIT IS NEEDED FOR RISER 8. DISCONNECTING MEANS NOT TO BE HIGHER THAN 6'7" TO OF DEVICE 9. NEED WATER & GAS BONDS |