Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07EL01037

Parcel: 126040940


Addresses:

649 N ERIN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/21/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAINTAIN WORKING CLEARANCES IN FRONT OF
SERVICE - 110.26
2. A PERMANENT METAL ADDRESS LABEL IS NEEDED
3. USE APPROVED FITTING WITH L.B - CHASE NIPPLE NOT APPROVED.
4. ONLY ONE GROUNDED CONDUCTOR PER LUG - 408.21
5. LABEL BREAKERS
6. BOND JUNCTION BOX ENCLOSURE
7. A LISTED BRACE KIT IS NEEDED FOR RISER
8. DISCONNECTING MEANS NOT TO BE HIGHER THAN 6'7" TO OF DEVICE
9. NEED WATER & GAS BONDS