Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND SINGLE GANG BELL BOX -- NEC 250.148 2. RECONNECT GROUND TO TELEPHONE SYSTEM 3. REMOVE PAINT AT GROUND CLAMP CONNECTION AT GAS PIPE - NEC 250.12 4. OPEN POSITIONS FOR BREAKERS ON PANEL WILL ALLOW BREAKERS TO BE INSTALLED HIGHER THAN 6'7" -- NEC 404.8 |