Permit: T07EL01034

Parcel: 128071060


Addresses:

6012 E OAK ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND SINGLE GANG BELL BOX -- NEC 250.148
2. RECONNECT GROUND TO TELEPHONE SYSTEM
3. REMOVE PAINT AT GROUND CLAMP CONNECTION AT
GAS PIPE - NEC 250.12
4. OPEN POSITIONS FOR BREAKERS ON PANEL WILL ALLOW BREAKERS TO BE INSTALLED HIGHER THAN 6'7" -- NEC 404.8