Permit: T07EL01021

Parcel: 116061040

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING. CANNOT USE SMASHED EMT WITH MINERALLAC STRAP -- NEC 230.28
2. REMOVE PAINT AT GROUND CLAMP CONNECTIONS --
NEC 250.12
3. INSTALL BREAKERS LISTED FOR USE IN PANEL -- NEC 110.3
4. SERVICE ENERGIZED PRIOR TO APPROVALS.