Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CUT STRANDS ON NEUTRAL & GROUND FEEDER TO SUITE 2. INSTALL PLASTIC BUSHING ON PVC WITH CONDUCTORS #4 AND LARGER PER NEC 352.46 & 300.4 3. IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD 4. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL. NEC 110.3 5. BOND AROUND REDUCING WASHERS - NEC 250.96 6. COMPLETELY DRIVE GROUND RODS - NEC 250.53 7. VERIFY GAS PIPE BOND - NEC 250.104 8. CANNOT USE 1/2" EMT AS SUPPORT FOR GROUNDING ELECTRODE CONDUCTOR - NEC 300.11 |