Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/26/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/05/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : 1. NEED TO PULL PERMITS FOR ALL WORK DONE & NEED TO HAVE APPROPRIATE INSPECTIONS ON THIS WORK. 2. NEED TO PROVIDE LADDER FOR ACCESS TO ATTIC 3. IT APPEARS MORE THAN THE REPAIR, THAT IS BEING STATED WAS DONE, BEEN DONE TO ELECTRIC SYSTEM 4. SERVICE UNSAFE TO ENERGIZE INTERIOR OF HOME MISSING WALL PLATES ON DEVICES. ALSO, MISSING LIGHTING FIXTURES. 5. COMPLETE ITEMS FROM PREVIOUS INSPECTION. 6. NEED TO BOND GAS & WATER TO SERVICE PER NEC 250.104 7. THIS MAY NOT BE COMPLETE LIST 8. NEUTRAL CONDUCTOR FROM SERVICE TO PANEL TO BE INSULATED & IDENTIFIED PER NEC 200.6 |