Permit: T07EL00986

Parcel: 117050480


Addresses:

411 N 4TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/19/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/14/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
06/13/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) SERVICE RISER NOT PROPERLY BONDED (BOND TO NEUTRAL) NEC 250.92
2) GROUND RODS TO BE MINIMUM 6' APART NEC 250.56
3) METAL PIPING BOND CONDUCTOR UNDERSIZED NEC 250.104
4) #6 AND SMALLER GROUND TO BE GREEN OR BARE ENTIRE LENGTH NEC 250.119
5) #6 AND SMALLER NEUTRAL TO WHITE ENTIRE LENGTH NEC 200.6
6) NOTE: WOULD BE A GOOD IDEA TO INSTALL A PARKING CURB IN FRONT OF SERVICE