Permit: T07EL00981

Parcel: 134050520


Addresses:

9405 E EL CAJON DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/08/2008 ELECTRIC - FINAL Approved
01/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/10/2007 ELECTRIC - FINAL Cancelled
07/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3
2. PANEL DIRECTORY PER NEC 408.4
3. ONE NEUTRAL PER TERMINAL NEC 408.21
4. EXTEND GROUNDING CONDUCTOR & TERMINATE AT GROUND BAR. CANNOT BE SPLICED WITH NEUTRAL CONDUCTOR.
5. INSTALL BUSHING AT HOLE IN BACK OF PANEL TO PROTECT WIRES NEC 300
6. REIDENTIFY WHITE WIRE ON 2 POLE 30 USED AS PHASE CONDUCTOR NEC 200.7
7. SECURE EMT WITHIN 3' OF PANEL - NEC 358.30
8. INSTALL CONNECTOR PROPERLY ON 3/4" EMT - NEC 110.3
9. CANNOT USE ROMEX IN WET LOCATION. ROMEX RUN IN 3/4" EMT -- NEC 334.12 & 100
10. PLEASE VERIFY PERMIT FOR NEW AC UNIT
11. INSTALL GROUND RODS
PER NEC 250.52, 250.53, 250.56, 250.64
12. BOND GAS & WATER PIPE PER NEC 250.104
13. SERVICE ENERGIZED PRIOR TO APPROVALS
14. PROTECT WIRE RUN THROUGH 1/2" EMT WITH PLASTIC BUSHING & SECURE 1/2" EMT PER NEC 312.5 & 300.15
15. INSTALL ROOF JACK ON RISER
16. SECURE RISER TO BUILDING.