Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TERMINATE GROUND WIRES PER MANUFACTURERS INSTRUCTIONS. CANNOT TERMINATE ALL GROUNDS UNDER ONE TERMINAL SCREW NEC 110.3 2) NEED DETAILED PANEL SCHEDULE. NO ABREVIATIONS NEC 408.4 3) SEAL OPENING IN BACK OF PANEL WERE WIRES COME THROUGH. USE NON COMBUSTIBLE MATERIAL |