Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CALLED AHEAD LEFT MESSAGE. NO CONTRACTOR ON SITE 2. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION TO AVOID REFEE HAVE COMPLETED BEFORE NEXT INSPECTION 3. GROUND RODS TO BE MIN. 6' APART |
|
| 12/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION 2. USE APPROVED STRAPS ON 1/2" EMT 3. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL 4. SINGLE GANG BELL BOX ON ROOF TO BE PROPERLY SUPPORTED |
|
| 06/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE #4 TO BUILDING SURFACE 2. UNABLE TO LOCATE GROUND RODS. PLEASE EXPOSE 3. PLEASE VERIFY PERMIT FOR NEW A/C UNIT 4. USE CONNECTIONS TO CONNECT EMT & CABLES TO 6" X 6" JUNCTION BOX 5. PROPERLY GROUND JUNCTION BOX 6" X 6" 6. INSTALL #10 GROUND & #10 NEUTRAL FOR DRYER CIRCUIT 7. CANNOT CONNECT GROUNDS & NEUTRALS TOGETHER IN JUNCTION BOX 8. #6 AND SMALLER NEUTRAL CONDUCTORS TO BE CONTINUOUSLY MARKED 9. SECURE SINGLE GANG BELL BOX TO BUILDING SURFACE 10. SERVICE ENERGIZED PRIOR TO APPROVALS. |