Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 06/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEUTRAL CONDUCTORS #6 & SMALLER NEED TO BE MARKED CONTINUOUSLY NEC 200.6 NEUTRAL AT GUEST HOUSE PANEL 2. VERIFY PERMIT FOR NEW A/C UNIT AT MAIN HOUSE |
|
| 05/24/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* INSTALL INSULATED NEUTRAL CONDUCTOR TO SUB-PANEL IDENTIFY NEUTRAL PER NEC 200.6 OK TO CLEAR INCR RESIDENTIAL UNITS #1 OR #2 |
|
| 05/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL WEATHERPROOF JUNCTION BOX FOR FEED TO SUB-PANEL. 2. INSTALL INSULATED GROUNDED (NEUTRAL) CONDUCTOR TO SUB-PANEL. IDENTIFY PER NEC 200.6 3. NEED BETTER DETAILED PANEL SCHEDULE PER NEC 408.4 4. INSTALL GROUNDING ELECTRODES AT GUEST HOUSE SERVICE PER NEC 250.50, 250.52, 250.53, 250.60, 250.66 5. BOND GAS & WATER TO SERVICE AT GUEST PER NEC 250.104 6. INSTALL LISTED MAST BRACING CANNOT USE EMT FOR BRACING OF MAST -- NEC 230.28 7. CANNOT USE COMPRESSION CONNECTORS FOR ATTACHMENT OF BRACING CUT & THREAD IMC OR RIGID CONDUIT. |