Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* FINISH PREVIOUS ITEMS |
|
| 06/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1. LABEL BREAKERS AS PER 408.4 - NO ABBREVIATIONS WHAT DISTINGUISHES ONE FROM ANOTHER 2. FILL UNUSED PORTION OF OPENINGS IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT 3. SHEATHING TO BE 1/4" MIN. INTO ENCLOSURE 4. TIGHTEN LOOSE LUG 5. CHASE NIPPLE NOT AN APPROVED FITTING FOR BOX OR L.B 6. COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 7. NEED TO BOND CONCENTRIC AT METER SOCKET 8. TIGHTEN GROUND TERMINATION AT TIME CLOCK 9. VERIFY BONDING JUMPER SIZE 250.66 10. MOUNTING HARDWARE NOT TO BE DRYWALL SCREWS 11. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR |
|
| 06/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. WHERE IS POWER FOR MONUMENT SIGN? - CIRCUIT TO BE AS PER 600.5 2. SERVICE LOCKED NO ACCESS |