Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2007 | ELECTRIC - FINAL | Approved | OK FINAL | |
| 09/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. LB COVER NOT ACCESSIBLE 2. PLEASE VERIFY TYPE CONDUCTOR FOR SUB-PANEL CORD NOT ALLOWED FOR PERMANENT WIRING 400.7 & 8 LIFE LINE NOT APPROVED 3. PROTECT CONDUCTORS AT NIPPLE 300.4 4. CHASE NIPPLE AT REDUCING WASHER NOT ALLOWED USE APPROVED FITTING TO PROVIDE GROUND FAULT PATH 5. USE CORRECT SIZED KO PLUG |
|
| 08/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CALL FOR FINAL ONCE CHANGED OVER |