Permit: T07EL00961

Parcel: 134101420


Addresses:

8132 E HAYNE ST

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
11/16/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
05/23/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING PER NEC 230.28
CANNOT USE SMASHED EMT & MINERALLAC STRAP
2. UNCOVER GROUND RODS. CAN ONLY LOCATE ONE & IT APPEARS TO BE CUT.
3. TERMINATE NEUTRAL CONDUCTOR ON NEUTRAL BAR AT SUB-PANEL NEC 408.21
4. INSTALL GROUND BAR AT SUB-PANEL & TERMINATE GROUNDS TO GROUND BAR -- NEC 408.20
5. INSTALL PLASTIC BUSHINGS AT CONNECTOR IN JUNCTION BOX TO PROTECT WIRES #4 AND LARGER -- NEC 300.4
6. SIZE EQUIPMENT GROUNDING CONDUCTOR RUN WITH FEEDERS PROPERLY -- NEC 250.122
7. CONNECT GROUND WIRE TO 12" X 12" JUNCTION BOX PER NEC 250.148
8. ARE ALUMINUM CONDUCTORS SPLICED TOGETHER WITH COPPER CONDUCTORS IN JUNCTION BOX.
9. SERVICE ENERGIZED PRIOR TO APPROVALS.
10. SIZE EQUIPMENT BONDING JUMPER PER NEC 250.102