Permit: T07EL00958

Parcel: 120021520


Addresses:

3926 S 13TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/29/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL 2 GROUNDS RODS 6' MIN. APART
BOND WATER & GAS PIPING PER 250 NEC
2. BRACE FOR RISER SUPPORT NEEDS TO BE A LISTED ASSEMBLY - HOMEMADE OUT OF BENT EMT NOT APPROVED.
3. CIRCUITS ON THE SAME BUSS CANNOT SHARE A SINGLE NEUTRAL.
4. NO ADDRESS LABEL.