Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL 2 GROUNDS RODS 6' MIN. APART BOND WATER & GAS PIPING PER 250 NEC 2. BRACE FOR RISER SUPPORT NEEDS TO BE A LISTED ASSEMBLY - HOMEMADE OUT OF BENT EMT NOT APPROVED. 3. CIRCUITS ON THE SAME BUSS CANNOT SHARE A SINGLE NEUTRAL. 4. NO ADDRESS LABEL. |