Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07EL00948
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/25/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL NEUTRAL TO METER FROM SERVICE. 2. INSTALL NEUTRAL KIT & MAIN BONDING JUMPER AT MAIN SERVICE DISCONNECT. 3. MARK SERVICE DISCONNECT PER NEC 230.20 4. BACK FED BREAKER TO BE FASTENED IN PLACE TO PANEL NEC 408.16 5. HAVE TRANSFORMER OPEN AT NEXT INSPECTION. 6. INSTALL FUSES AT SERVICE DISCONNECT. 7. VERIFY 3/0 IS BUILDING UFER. |