Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/25/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL NEUTRAL TO METER FROM SERVICE. 2. INSTALL NEUTRAL KIT & MAIN BONDING JUMPER AT MAIN SERVICE DISCONNECT. 3. MARK SERVICE DISCONNECT PER NEC 230.20 4. BACK FED BREAKER TO BE FASTENED IN PLACE TO PANEL NEC 408.16 5. HAVE TRANSFORMER OPEN AT NEXT INSPECTION. 6. INSTALL FUSES AT SERVICE DISCONNECT. 7. VERIFY 3/0 IS BUILDING UFER. |