Permit: T07EL00948

Parcel: 128100810

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07EL00948

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/29/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/25/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL NEUTRAL TO METER FROM SERVICE.
2. INSTALL NEUTRAL KIT & MAIN BONDING JUMPER AT MAIN SERVICE DISCONNECT.
3. MARK SERVICE DISCONNECT PER NEC 230.20
4. BACK FED BREAKER TO BE FASTENED IN PLACE TO PANEL NEC 408.16
5. HAVE TRANSFORMER OPEN AT NEXT INSPECTION.
6. INSTALL FUSES AT SERVICE DISCONNECT.
7. VERIFY 3/0 IS BUILDING UFER.