Permit: T07EL00944


Addresses:

1007 E IRWIN PL

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY PANEL DIRECTORY IN PANEL -
NOT SHARPIE - NEC 408.4
2. STILL HAVE SHORT IN LIGHTING CKT - BREAKER TRIPS

A REINSPECTION FEE WILL BE CHARGED IF NOT CORRECT NEXT TIME.
08/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LABEL ALL CIRCUITS IN PANEL NEC 408.4
2. INSTALL 2 POLE 20 AMP BREAKER FOR 240V CIRCUIT FEEDING TIME CLOCK
3. BREAKER FOR WEST LIGHTS IS TRAPPED
4. PROVIDE HAND HOLE TO ACCESS WIRING OR PROVIDE HINGED POLE BASE PER NEC 410.15 (B)
06/29/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PVC CONDUITS TO BE BURIED AS PER 300.5 PORTIONS OF CONDUIT COVERED WITHOUT INSPECTION UNCOVER
2. ADDRESS LABEL TO BE PERMANENT METAL
3. PLEASE VERIFY SCHEDULE 80 CONDUIT ABOVE GRADE
4. LABEL BREAKERS AS PER 408.4
5. TEMP SERVICE OUTLET NOT ON PLANS