Date Description Inspector Results Comments
09/24/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PARTIAL INSPECTION FOR SERVICE AND FEEDER TO EXISTING A, B & C PANEL
2) PROVIDE PHYSICAL PROTECTION FOR SERVICE (BOLLARDS, CURBS ETC...)
3) PROPERLY TERMINATE GUTTER GROUNDS
4) RESECURE DISCONNECTS
5) IDENTIFIY DISCONNECTS
6) IDENTIFY EXISTING EQUIPMENT/PANELS AT SERVICE
7) INSTALL MISSING KO'S, REMOVE LOAD SIDE NEUTRAL BONDING SCREWS