Permit: T07EL00941

Parcel: 10706043B

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T07EL00941

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
08/06/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
08/02/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL AND TERMINATE SERVICE SECONDARY CONDUCTORS
2. NEED BUSHING OR BELL END ON PVC - NEC 352.46
3. PLANS SHOW A SURGE SUPPRESSOR
4. FEEDER RACEWAYS NOT TO TERMINATE/BLOCK REMOVAL OF ACCESS PANELS - NEC 110.3 B
5. WATER BOND CLAMP NOT USED PROPERTLY - NEC 110.3
6. CHECK GROUNDING ELECTRODE FOR TRANSFORMER -
NEC 250
7. PROVIDE RACEWAY FOR #8 TRANSFORMER GROUNDING ELECTRODE CONDUCTOR - NEC 250.64B
07/31/2007 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
- RECEIVED LETTER OF TORQUE
- INSTALL FUSES & R-PINS
- OK NEUTRAL BOND JUMPER