Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T07EL00941
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
08/02/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL AND TERMINATE SERVICE SECONDARY CONDUCTORS 2. NEED BUSHING OR BELL END ON PVC - NEC 352.46 3. PLANS SHOW A SURGE SUPPRESSOR 4. FEEDER RACEWAYS NOT TO TERMINATE/BLOCK REMOVAL OF ACCESS PANELS - NEC 110.3 B 5. WATER BOND CLAMP NOT USED PROPERTLY - NEC 110.3 6. CHECK GROUNDING ELECTRODE FOR TRANSFORMER - NEC 250 7. PROVIDE RACEWAY FOR #8 TRANSFORMER GROUNDING ELECTRODE CONDUCTOR - NEC 250.64B |
|
07/31/2007 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* - RECEIVED LETTER OF TORQUE - INSTALL FUSES & R-PINS - OK NEUTRAL BOND JUMPER |