Permit: T07EL00940

Parcel: 106022590


Addresses:

303 W KING RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BRACES SHOULD BE BEHIND RISER
2. ALSO, THERE SHOULD BE AN "A AND B" ON PERMIT
IN ORDER TO CLEAR TO TEP
05/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/25/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
COMPLETE NOTES #4 & #1
05/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BRACE FOR RISER CONDUIT NOT EFFECTIVE WHERE INSTALLED. BRACE SUPPORTS SHOULD BE INSTALLED TO PREVENT STRESS IN DIRECTION OF UTILITY DROP CONDUCTORS.
2. CONDUCTORS NOT IN RACEWAY OR CABLE SHEATH WHERE GOING THRU WALL AT UNIT #2
3. SHEETMETAL SCREW NOT ALLOWED FOR BONDING IN J-BOX PER 250 NEC.
4. COMPLETE GROUNDING AT UNIT #1
5. LABEL SERVICE