Permit: T07EL00934

Parcel: 11104170A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/08/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK CORRECTIONS

1. PARKING CURB TO BE MINIMUM 36" FROM FRONT OF SERVICE - NEC 110.26
2. FEEDER EQUIPMENT GROUND TO BE GREEN OR BARE ENTIRE LENGTH - NEC 250.119
3. REMOVE PAINT UNDERGROUND LUGS - NEC 250.12
4. SHEETMETAL SCREW NOT ALLOWED FOR PANEL GROUND
NEC 250.8
5. MISSING STRUT STRAP FOR EMT ON ROOF
6. NEED OXIDE INHIBITOR ON ALL ALUMINUM TERMINATIONS
09/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PARKING CURB TO BE NO CLOSER THAN 36" IN FRONT OF SERVICE -- NEC 110.26
2. SELF-TAP SCREWS NOT ALLOWED FOR GROUNDING CONNECTIONS - NEC 250.8
3. PROPERLY IDENTIFY FEEDER EQUIPMENT GROUND
NEC 250.119
4. PARKING CURB TO BE FULL WIDTH AND SECURED IN PLACE
5. PROVIDE LADDER AND INTERIOR ACCESS, HAVE SERVICE OPEN FOR INSPECTION (COULD NOT TURN SCREWS) INSTALL MISSING COVER SCREW.
07/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NOTE: PROVIDE PROTECTION IN FRONT OF SERVICE BEFORE FINAL, SUCH AS BOLLARDS OR A PARKING CURB SECURED IN PLACE-SEE NEC 110.27 B
05/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING PER NEC 230.28
CANNOT USE EMT WITH SMASHED ENDS.
2. 400 AMP SERVICE UPGRADE. NOT A SIMPLE SERVICE UPGRADE. NEED TO HAVE APPROVED SET OF PLANS. INSTALLING 400 AMP 4 METER PACK.