Permit: T07EL00931

Parcel: 115020910


Addresses:

449 E LESTER ST

Inspection Status: Closed

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/09/2008 ELECTRIC - FINAL Closed REFERENCE T08EL01728
05/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED 2 GROUND RODS MIN. 6' APART -- NEC 250.53
2. NEED TO BOND BOTH ENDS OF METAL RACEWAY TO GROUNDING ELECTRODE CONDUCTOR -- NEC 250.64
3. SECURE RISER TO BUILDING