Inspection History Details
Inspection Status: Closed
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2008 | ELECTRIC - FINAL | Closed | REFERENCE T08EL01728 | |
| 05/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED 2 GROUND RODS MIN. 6' APART -- NEC 250.53 2. NEED TO BOND BOTH ENDS OF METAL RACEWAY TO GROUNDING ELECTRODE CONDUCTOR -- NEC 250.64 3. SECURE RISER TO BUILDING |