Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL METER OPENING PANEL B 2. NEED MAIN HOLDDOWN DEVICE PANEL B - NEC 408 3. IDENTIFY PANEL A & B 4. #6 & SMALLER GROUND TO BE GREEN ENTIRE LENGTH (OR BARE) -- NEC 250.119 |