Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07EL00929

Parcel: 11307255B

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL METER OPENING PANEL B
2. NEED MAIN HOLDDOWN DEVICE PANEL B - NEC 408
3. IDENTIFY PANEL A & B
4. #6 & SMALLER GROUND TO BE GREEN ENTIRE LENGTH
(OR BARE) -- NEC 250.119