Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/10/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND GAS PIPING ON HOUSE SIDE OF METER 2) INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL 3) INSTALL ANTI-OXIDATION COMPOUND ON ALUMINIUM TERMINATIONS 4) INSTALL SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER SECTION. SEE INSTRUCTIONS ON PANL DOOR |