Permit: T07EL00880

Parcel: 12216224A


Addresses:

1825 N ALVERNON WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EQUIPMENT GROUND #6 & SMALLER TO BE GREEN ENTIRE LENGTH - NEC 250.119
2. WHY 2 GROUNDS TO PANEL/GUTTER IN CHURCH?
3. BONDING CONDUCTOR FOR NIPPLE BETWEEN CT CAN AND PANEL IS UNDERSIZED - NEC 250.102C
4. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.70B
5. PROPERLY IDENTIFY PANEL DIRECTORY AND NUMBER BREAKERS - NEC 408.4
6. RECEPTACLES TO BE GFI PROTECTED
7. GROUND ALL BOXES
8. BOXES TO BE WEATHERPROOF
9. STRAP FLEX WITHIN 12" OF TERMINATIONS
10. HAVE OPEN WIRING AT WALL
11. DRIVE GROUND RODS FLUSH, SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE
12. INSTALL BULB FOR SERVICE LIGHT
08/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE RESCHEDULE WHEN CONTR. CAN BE ON SITE
ADDRESS LABEL ON METER NOT LEGIBLE