Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT GROUND #6 & SMALLER TO BE GREEN ENTIRE LENGTH - NEC 250.119 2. WHY 2 GROUNDS TO PANEL/GUTTER IN CHURCH? 3. BONDING CONDUCTOR FOR NIPPLE BETWEEN CT CAN AND PANEL IS UNDERSIZED - NEC 250.102C 4. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.70B 5. PROPERLY IDENTIFY PANEL DIRECTORY AND NUMBER BREAKERS - NEC 408.4 6. RECEPTACLES TO BE GFI PROTECTED 7. GROUND ALL BOXES 8. BOXES TO BE WEATHERPROOF 9. STRAP FLEX WITHIN 12" OF TERMINATIONS 10. HAVE OPEN WIRING AT WALL 11. DRIVE GROUND RODS FLUSH, SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 12. INSTALL BULB FOR SERVICE LIGHT |
|
| 08/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE RESCHEDULE WHEN CONTR. CAN BE ON SITE ADDRESS LABEL ON METER NOT LEGIBLE |