Permit: T07EL00880

Parcel: 12216224A


Addresses:

1825 N ALVERNON WY

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/12/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
NOTE: TIGHTEN ALL SCREWS FOR CLAMPS TO GROUND RODS AND GAS PIPE
10/10/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE PROPER CLAMPS FOR CONDUCTOR TO GROUND RODS AND GAS PIPE
2. SERVICE NIPPLE BOND STILL UNDERSIZED (BOND IN PANEL BOARD SIDE)
08/14/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/02/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/08/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) CHECK LOAD SIDE AFTER ENERGIZED
06/05/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. MOVE GROUNDING ELECTRODE CONDUCTOR OUT OF CT CAN AND INTO MAIN DISCONNECT
2. PLEASE HAVE ENGINEER VERIFY OLD CLOTH COVERED CONDUCTOR FOR USAGE
3. MAINTAIN WORKING CLEARANCES AT ELECTRICAL EQUIPMENT
4. DOOR TO OPEN 90 DEG.
06/04/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*