Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* NOTE: TIGHTEN ALL SCREWS FOR CLAMPS TO GROUND RODS AND GAS PIPE |
|
| 10/10/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE PROPER CLAMPS FOR CONDUCTOR TO GROUND RODS AND GAS PIPE 2. SERVICE NIPPLE BOND STILL UNDERSIZED (BOND IN PANEL BOARD SIDE) |
|
| 08/14/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/02/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/08/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CHECK LOAD SIDE AFTER ENERGIZED |
|
| 06/05/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. MOVE GROUNDING ELECTRODE CONDUCTOR OUT OF CT CAN AND INTO MAIN DISCONNECT 2. PLEASE HAVE ENGINEER VERIFY OLD CLOTH COVERED CONDUCTOR FOR USAGE 3. MAINTAIN WORKING CLEARANCES AT ELECTRICAL EQUIPMENT 4. DOOR TO OPEN 90 DEG. |
|
| 06/04/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |