Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND ROD TO BE IN SERIES NOT PARALLEL 2. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 3. SINGLE GANG W/P BOX HAS CONDUCTOR OVERFILL 4. TERMINATE GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS 5. RECEPTACLE COVER UNDER PANEL TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 6. CORRECTLY LABEL BREAKERS 7. SECURE GROUND CONDUCTOR TO STRUCUTRE 8. PLEASE VERIFY QUALIFIED ELECTRICAL PERSON |
|
| 05/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1. (2) GROUND RODS REQUIRED MIN 6' APART 2. VERIFY GAS PIPING BOND 3. RISER BRACE NEEDS TO BE LISTED ASSEMBLY 4. USE MIN. 1/4" BOLTS FOR RISER STRAP 5. USE PROPER BUSHING BEHIND PANEL 6. ALL CIRCUIT BREAKERS TO BE OF SAME MANUF. AS PANEL 7. PROVIDE BUSHED CONNECTORS AT ENDS OF EMT SLEEVES TO PROTECT CABLE FROM ABRASION. |