Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MARK SERVICE DISCONNECT PER NEC 230.70 2. NEED DETAILED PANEL SCHEDULE PER NEC 408.4 3. PROVIDE INSTALLATION INSTRUCTIONS FOR CLASSIFIED 2 POLE 40A CIRCUIT BREAKER. 4. NEED TO BOND SERVICE RISER & OFFSET NIPPLE PER NEC 250.92 & SIZE PER NEC 250.102 5. INSTALL GROUNDING ELECTRODES PER NEC 250 SECTION 3 6. OFFSET NIPPLE NOT COMPLETELY TIGHTENED 7. INSTALL ON ALUMINUM TERMINATIONS 8. MISSING SCREW FOR DEAD FRONT 9. VERIFY BONDING OF GAS & WATER PER NEC 250.104 10. SERVICE ENERGIZED PRIOR TO APPROVALS. |