Permit: T07EL00861

Parcel: 133041950


Addresses:

9351 E CALLE KUEHN

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/05/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MARK SERVICE DISCONNECT PER NEC 230.70
2. NEED DETAILED PANEL SCHEDULE PER NEC 408.4
3. PROVIDE INSTALLATION INSTRUCTIONS FOR CLASSIFIED 2 POLE 40A CIRCUIT BREAKER.
4. NEED TO BOND SERVICE RISER & OFFSET NIPPLE
PER NEC 250.92 & SIZE PER NEC 250.102
5. INSTALL GROUNDING ELECTRODES PER NEC 250 SECTION 3
6. OFFSET NIPPLE NOT COMPLETELY TIGHTENED
7. INSTALL ON ALUMINUM TERMINATIONS
8. MISSING SCREW FOR DEAD FRONT
9. VERIFY BONDING OF GAS & WATER PER NEC 250.104
10. SERVICE ENERGIZED PRIOR TO APPROVALS.