Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07EL00860

Parcel: 126061540


Addresses:

4058 E ROBERTS PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #1 OF PREVIOUS INSPECTION
08/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE 18 CURRENT CARRYING CONDUCTORS IN 2" EMT NEED TO DERATE - NEC 310.15
2. (2) GANG BELL BOX NOT PROPERLY SIZED FOR NUMBER OF CONDUCTORS. NEC 314.16
3. GROUND ALL METAL BOXES - NEC 314.4
4. PULL PROPER SIZE GROUND TO ALL BOXES FOR OVERCURRENT DEVICE SIZE - NEC 250.122
5. #6 & SMALLER NEUTRAL CONDUCTORS TO BE IDENTIFIED ENTIRE LENGTH - NEC 200.6
6. TIGHTEN ALL FITTINGS
7. PROTECT WIRES THROUGH BACK OF BOXES FROM DAMAGE
NEC 300.4
8. LABEL ALL CIRCUITS - NEC 408.4
9. 3/4" TO (2) GANG BELL BOX MAY BE OVERFILLED.
PLEASE VERIFY.
10. VERIFY GAS BOND
11. HAVE LADDER FOR NEXT INSPECTION