Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/06/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #1 OF PREVIOUS INSPECTION |
|
| 08/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE 18 CURRENT CARRYING CONDUCTORS IN 2" EMT NEED TO DERATE - NEC 310.15 2. (2) GANG BELL BOX NOT PROPERLY SIZED FOR NUMBER OF CONDUCTORS. NEC 314.16 3. GROUND ALL METAL BOXES - NEC 314.4 4. PULL PROPER SIZE GROUND TO ALL BOXES FOR OVERCURRENT DEVICE SIZE - NEC 250.122 5. #6 & SMALLER NEUTRAL CONDUCTORS TO BE IDENTIFIED ENTIRE LENGTH - NEC 200.6 6. TIGHTEN ALL FITTINGS 7. PROTECT WIRES THROUGH BACK OF BOXES FROM DAMAGE NEC 300.4 8. LABEL ALL CIRCUITS - NEC 408.4 9. 3/4" TO (2) GANG BELL BOX MAY BE OVERFILLED. PLEASE VERIFY. 10. VERIFY GAS BOND 11. HAVE LADDER FOR NEXT INSPECTION |